An air-conditioning unit with a zeotropic mixture controlled by a distillation column
We describe a new air-conditioning and heat-pump system, which may be used to separate a refrigerant mixture efficiently and adjust the composition in the system with cooling- or heating-load changes. A dynamic model has been developed to analyze the transient behavior of the capacity-control system. An air conditioner equipped with a small distillation circuit has been tested. Increases in the SEERs (seasonal energy efficiency ratios) for the new composition-controlled system are 28.3 and 17.7% and capacity changes 57.3–91.8% and 71.5–101%, respectively, for R22/142b and R23/124.
Year of publication: |
1998
|
---|---|
Authors: | ZHAO, YANG ; YITAI, MA ; SANYUAN, ZHAO ; YIE, LI |
Published in: |
Energy. - Elsevier, ISSN 0360-5442. - Vol. 23.1998, 9, p. 777-784
|
Publisher: |
Elsevier |
Saved in:
Online Resource
Saved in favorites
Similar items by person
-
A heat-pump system for heat recovery at a substation
Zhao, Yang, (1995)
-
Zhao, Yang, (1997)
-
Shitong, Zha, (2003)